Energy storage and batteries

GB/T 36276

GB/T 36276-2023 Lithium-ion batteries for electrical energy storage (《电力储能用锂离子电池》)

GB/T 36276-2023 sets performance and safety requirements for lithium-ion battery cells, modules and clusters used in electrical energy storage. Its key safety tests are cell thermal runaway and module thermal runaway propagation.

Within CNAS accreditation Clause 6.7.4.2.1 (initial thermal runaway test), clause 6.7.4.3 (thermal runaway propagation test) and clause 6.7.1.5.1 (battery module insulation test, test voltage not exceeding 500 V) are within our CNAS scope.

Cell thermal runaway

When a cell goes into thermal runaway at any point in its service life, its surface temperature must be above 90 °C. After thermal runaway the cell must not catch fire or explode, and must not rupture anywhere other than its explosion-proof valve or pressure relief point.

Module thermal runaway propagation

  1. Carry out the initialisation charge of the battery module.
  2. Trigger thermal runaway in a single cell, the trigger object, by overcharge or heating. Heat generated by the trigger object should pass easily to the adjacent cells.
  3. Overcharge trigger: charge at a constant current of at least 1/3 C, or not more than the maximum operating current, until thermal runaway occurs or 200 % SOC is reached. Adjacent cells must not be overcharged. If thermal runaway does not occur, observe for a further 1 h.
  4. Heating trigger: heat continuously at the heater's maximum power, and stop when thermal runaway occurs or the monitoring point reaches 300 °C. If thermal runaway does not occur, observe for a further 1 h.
  5. Record the test results.

How it relates to UL 9540A

Both trigger thermal runaway by heating and other means, but for different purposes: GB/T 36276 is a product safety test with pass/fail criteria, while UL 9540A is a test method that provides fire data for installation approval. Where a project needs results for both export and the Chinese market, the samples and trigger methods can be planned together.

Our accredited scope

AccreditationStandardTest items
CNAS GB/T 36276-2023
Lithium-ion batteries for electrical energy storage (China)
  • Module insulation (cl. 6.7.1.5.1)
  • Initial thermal runaway (cl. 6.7.4.2.1)
  • Thermal runaway propagation (cl. 6.7.4.3)
CMA GB/T 36276-2023
Lithium-ion batteries for electrical energy storage (China)
  • Initial thermal runaway – Lithium-ion batteries for electrical energy storage: cells (cl. 6.7.4.2.1)
  • Insulation test – Lithium-ion batteries for electrical energy storage: modules (cl. 6.7.1.5.1; Only test voltages up to 500 V)
  • Thermal runaway propagation – Lithium-ion batteries for electrical energy storage: modules (cl. 6.7.4.3)

From our CNAS accreditation scope and our CMA approval (China's mandatory approval for inspection and testing bodies, needed for reports used in mainland China), as of 2026-10. Items not listed are outside the scope; ask our engineers whether they can be tested.

Through our partner laboratory

StandardTest items
GB/T 36276-2023
Lithium-ion batteries for electrical energy storage (electrical performance)
  • Appearance, dimensions and mass
  • Initial charge/discharge performance at 25 ℃
  • Initial charge/discharge performance at 45 ℃
  • Initial charge/discharge performance at 5 ℃
  • Power characteristics
  • Rate charge/discharge performance
  • Energy retention and recovery
  • High-temperature adaptability
  • Low-temperature adaptability
  • Initial charge/discharge performance at high altitude
  • Storage performance
  • Cycle performance
  • Cyclic damp heat
  • Alarm and protection functions

These tests are carried out by a Huahui strategic partner laboratory that holds the relevant CMA approval in China. They are outside Huahui’s own CNAS / CMA scope. Ask our engineers about specimen size, current, voltage and other conditions.

Frequently asked questions

How is thermal runaway of a cell determined?

The indicators are a voltage drop in the test object, the temperature at a monitoring point reaching the battery protection temperature, and a temperature rise rate at a monitoring point of at least 1 °C/s. Thermal runaway is deemed to have occurred when a voltage drop and that rise rate occur together, or when the protection temperature is reached together with that rise rate. Fire or explosion during heating or within 1 hour after heating ends is also judged as thermal runaway.

Can you test electrical performance, such as initial charge/discharge and cycling?

Yes. Initial charge/discharge, power, rate, energy retention and recovery, high- and low-temperature adaptability, high altitude, storage, cycling, cyclic damp heat and alarm/protection tests are carried out by a Huahui strategic partner laboratory (see Through our partner laboratory below). Thermal runaway and the other safety tests are carried out at Huahui.