What it tests
Factories, warehouses and laboratories often store lithium-ion batteries and power-tool packs in dedicated cabinets. UL 1487, published in February 2025 for the US and Canada, is the first standard specifically for these battery containment enclosures. It addresses three hazards of thermal runaway — heat, fire and deflagration — but not toxicity.
Performance tests:
| Section | Test | What is checked |
|---|---|---|
| 14 | Endurance cycling | After repeated cycling, self-closing doors, self-closing and self-latching mechanisms, handles and hinges still work as intended |
| 15 | Weight loading | After 72 hours with 120 % of the rated load of inert weights in each storage cavity, doors, shelves, dividers and so on still work |
| 16 | Internal thermal runaway | Thermal runaway is initiated in test cell packs inside; no charring or ignition of the cheesecloth indicator, no external flaming, no effluent gas release other than through dedicated vents, and temperatures within limits |
| 17 | Internal deflagration | A flammable mixture inside is ignited; no rupture, no ejection of fragments, no collapse of storage cavities, and no external flaming except through pressure-relief devices or dedicated vents |
| Annex D | External fire | Optional: at the request of the manufacturer or authority having jurisdiction, the enclosure's resistance to an external fire |
Testing at Huahui
We can carry out all the tests of UL 1487, sections 14 to 17 and Annex D. The internal thermal runaway test runs under a collection hood that captures all effluent gases, smoke and products of combustion. These tests are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.
For the heat and abrasion resistance of battery enclosure materials themselves, see UL 2596; for thermal runaway propagation in energy storage systems, see UL 9540A.
Available, not accredited
| Standard | Test items |
|---|---|
| ANSI/CAN/UL/ULC 1487:2025 Battery containment enclosures |
|
We can carry out these tests, but they are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark. If the results are for certification, check first that your certifier accepts them.
Frequently asked questions
How does UL 1487 differ from UL 9540A?
UL 9540A evaluates thermal runaway propagation in an energy storage system itself. UL 1487 evaluates whether an enclosure used to store batteries contains the thermal runaway, fire and deflagration of the batteries inside. UL 1487 explicitly excludes energy storage systems, which fall under UL 9540.
Can the enclosure include charging?
Yes. The standard allows enclosures with integral systems, or with internal power distribution for charging the cells, batteries, packs or battery-powered devices inside.