What it tests
When a cell goes into thermal runaway, the pack enclosure faces two attacks: hot flame and particles ejected from the cell, and heat and pressure inside the pack. UL 2596 sets a test method for each, used to compare enclosure materials for electric vehicle and energy storage batteries — metals, composites, coatings, insulation layers and so on.
Section 5: torch and grit (TaG) test
- Specimens 200 mm × 200 mm, at the thickness used in the product.
- A methane-oxygen torch produces a nominal 3 kW flame, verified each test day at 1200 ± 50 °C.
- The specimen surface is 60 mm from the torch outlet, and the flame carries abrasive particles, like the ejecta of a thermal runaway.
Section 6: thermal runaway exposure test
- A fuel package of 25 lithium-ion 18650 cells (NCA cathode) inside a five-sided steel test box.
- The specimen is sealed onto the open side as the sixth face; a side vent is sized for the target peak pressure.
- All cells go into thermal runaway; box temperature, pressure and the specimen's unexposed-face temperature are recorded. Three specimens per material.
Testing at Huahui
We can carry out both the section 5 TaG test and the section 6 thermal runaway exposure test, with a dedicated TaG rig and test box, at our Shanghai main laboratory. They are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.
For cabinets used to store batteries, see UL 1487; for battery thermal runaway testing, see battery thermal runaway testing.
Available, not accredited
| Standard | Test items |
|---|---|
| UL 2596:2023 Thermal and mechanical performance of battery enclosure materials |
|
We can carry out these tests, but they are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark. If the results are for certification, check first that your certifier accepts them.
Frequently asked questions
Do UL 2596 results show that a battery pack is safe?
Not on their own. The standard says the material performance measured by these methods shall not be assumed to correlate with performance in the end-use application. It is a tool to compare and screen enclosure materials; the safety of a complete pack is evaluated under the relevant product standard.