Reaction to fire: materials

ISO 9705-1

ISO 9705-1:2016, Reaction to fire tests — Room corner test for wall and ceiling lining products — Part 1: Test method for a small room configuration

ISO 9705-1 lines the walls and ceiling of a full-size small room with the product, ignites it in a corner and measures heat release and smoke, covering a fire's early stages from ignition up to flashover. We can carry it out; it is not currently within our accreditation.

Available, outside accreditation scope We can carry out the ISO 9705-1:2016 room corner test. It is not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.

What it tests

Small-scale fire tests look at the material alone; whether wall and ceiling linings drive a fire in a real room needs a full-size room. ISO 9705-1 does this:

  • Room: a small room of 3.6 m × 2.4 m × 2.4 m inside, with a 0.8 m × 2.0 m doorway in the centre of one 2.4 m × 2.4 m wall, no other ventilation, and the product on the walls and ceiling.
  • Fire source: a propane burner in a corner opposite the doorway wall, at 100 kW for the first 10 minutes after ignition, then 300 kW for a further 10 minutes.
  • Measurements: all combustion products leaving the doorway are collected by a hood, and heat release rate, smoke production and the fire growth rate (FIGRA) are measured in the exhaust duct.
  • End: 20 minutes after ignition, or earlier at flashover — when the heat release rate of burner and product together (30-second sliding average) reaches 1000 kW.

The test gives data for the early stages of a fire, from ignition up to flashover; it does not evaluate fire resistance.

Testing at Huahui

We can carry out the ISO 9705-1:2016 room corner test, using the collection hood and heat release measurement system of our UL 9540A large-scale testing. It is not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.

For sandwich panel building systems see ISO 13784-1 and GB/T 25206.1; for the single burning item test see EN 13823.

Available, not accredited

StandardTest items
ISO 9705-1:2016
Room corner test for wall and ceiling lining products — Part 1: Small room configuration
  • Room corner test of wall and ceiling lining products

We can carry out these tests, but they are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark. If the results are for certification, check first that your certifier accepts them.

Frequently asked questions

Can sandwich panels or floor coverings be tested this way?

No. The standard does not cover floor coverings, and sandwich panel building systems, pipe insulation and facades have their own standards: ISO 13784, ISO 20632 and ISO 13785. For sandwich panels see ISO 13784-1.