What it tests
Sandwich panels mostly have steel faces and a core of plastic foam, mineral wool or glass wool. Small-scale material tests cannot show how fire travels in the core or along the joints; ISO 13784-1 looks at it in a full-size room:
- Room: the panels form a room with internal dimensions of 3.6 m × 2.4 m × 2.4 m, four walls and a ceiling, connected as in end use, with a 0.8 m × 2.0 m doorway in the centre of one 2.4 m × 2.4 m wall.
- Fire source: a propane burner in an inside corner at 100 kW for the first 10 minutes, then 300 kW for a further 10 minutes, followed by 10 minutes of observation with the burner off.
- Measurements: heat and smoke release (by the ISO 9705 method or the method of Annex B), and temperatures on the panel surfaces, in the core and in the doorway.
- Observations: flame spread on the surface and in the core, joint opening, delamination, falling debris and flaming droplets, flames out of the doorway, structural collapse.
- End: flashover (combined heat release rate of burner and specimen reaching 1000 kW for more than 10 s) or 30 minutes, whichever comes first.
The Chinese counterpart is GB/T 25206.1; lining products are tested to ISO 9705-1.
Testing at Huahui
We can carry out the ISO 13784-1:2014 small room test, using the collection hood and heat release measurement system of our UL 9540A large-scale testing. It is not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.
Available, not accredited
| Standard | Test items |
|---|---|
| ISO 13784-1:2014 Reaction-to-fire tests for sandwich panel building systems — Part 1: Small room test |
|
We can carry out these tests, but they are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark. If the results are for certification, check first that your certifier accepts them.
Frequently asked questions
Which method applies to panels used as linings on a wall?
Lining products supported by, bonded or nailed to an underlying wall or ceiling are tested to ISO 9705. ISO 13784-1 covers free-standing, self-supporting and frame-supported sandwich panel systems that form the room themselves.
Does this test show fire resistance?
No. The standard states that the method does not assess fire resistance, which is tested by other methods such as EN 1364 or UL 263.