What it tests
GB/T 25206 has two parts: Part 1, small rooms, and Part 2, large rooms. Part 1 was published in June 2014 and took effect in October 2014, as a modified adoption of ISO 13784-1:2002.
- Room: the panels form a room with internal dimensions of 3.6 m × 2.4 m × 2.4 m on a rigid non-combustible floor, with a 0.8 m × 2.0 m opening in the centre of one 2.4 m × 2.4 m wall and no other ventilation openings.
- Ignition source: a sand-filled propane burner with a 170 mm × 170 mm top, in the corner or at a joint.
- Output: 100 kW for the first 10 minutes, 300 kW for the second 10 minutes, then the burner is turned off and observation continues for 10 minutes.
- Measurements: heat and smoke release, and temperatures on the panel faces and in the core to follow flame spread inside the core.
- End: flashover (for example a heat release rate of 1000 kW) or 30 minutes; earlier if the structure collapses or staff are at risk.
The results are used to assess the building system's contribution to fire growth up to flashover, the potential for fire to spread outside, to other compartments or to neighbouring buildings, the risk of collapse, and the development of smoke in the room.
For the international counterpart, see ISO 13784-1 (current edition 2014).
Testing at Huahui
We can carry out the GB/T 25206.1-2014 small room test, using the collection hood and heat release measurement system of our UL 9540A large-scale testing. It is not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.
Available, not accredited
| Standard | Test items |
|---|---|
| GB/T 25206.1-2014 Reaction to fire of sandwich panel building systems — Part 1: Small room method |
|
We can carry out these tests, but they are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark. If the results are for certification, check first that your certifier accepts them.