Chinese standards: fire doors, windows, shutters and glass GB 12955
GB 12955-2024 Fire doors (《防火门》); also GB 12955-2008
GB 12955 is the Chinese product standard for fire doors. It sets requirements for classification, materials, hardware, fire resistance, opening and closing, and mechanical performance. For the 2024 edition, fire resistance, hose stream resistance, durability under repeated opening and closing, mechanical performance and fire resistance of locks and hinges are within our CNAS scope.
Within CNAS accreditation GB 12955-2024 clauses 7.3, 7.4, 7.7.1–7.7.4, 7.8, 7.10, 7.11 and Annex B are within our CNAS scope; further items of the 2008 and 2024 editions are within our CMA approval scope, as listed in the table below.
What GB 12955 tests
Fire door testing falls into several parts:
- Fire resistance: the complete doorset is exposed on a furnace to the standard time–temperature curve and assessed for integrity and insulation; the test method is GB/T 7633;
- Hose stream resistance;
- Mechanical performance: resistance to vertical load (GB/T 29049), resistance to static torsion (GB/T 29530) and resistance to soft heavy body impact (GB/T 14155);
- Opening, closing and linkage: durability under repeated opening and closing, and receiving linkage signals and sending feedback;
- Appearance, dimensions and materials: appearance and dimensional deviations; the 2008 edition also covers moisture content of timber and wood-based panels, steel thickness, door leaf mass and other items;
- Hardware fire resistance: fire resistance of locks, hinges and other hardware.
Testing at Huahui
Tests run at our Shanghai main laboratory. Fire resistance is tested on the vertical furnace, and the mechanical and opening and closing items are done in the same laboratory, so one batch of samples can cover all the items needed for type testing.
For what to watch for when testing to the new edition, see our article Testing fire doors to the new GB 12955-2024: what to watch for. For fire doors for export, see UL 10B / UL 10C and EN 1634-1.
Our accredited scope
| Accreditation | Standard | Test items |
| CNAS | GB 12955-2024 Fire doors | - Fire resistance (cl. 7.10)
- Hose stream resistance (cl. 7.11)
- Appearance (cl. 7.3)
- Dimensional deviation (cl. 7.4)
- Durability under repeated opening and closing (cl. 7.7.1)
- Resistance to vertical load (cl. 7.7.2)
- Resistance to static torsion (cl. 7.7.3)
- Resistance to soft and heavy body impact (cl. 7.7.4)
- Receiving and feeding back linkage signals (cl. 7.8)
- Fire resistance – Locks and hinges (Annex B)
|
| CMA | GB 12955-2024 Fire doors | - Appearance (cl. 7.3)
- Dimensional deviation (cl. 7.4)
- Durability under repeated opening and closing (cl. 7.7.1)
- Resistance to vertical load (cl. 7.7.2)
- Resistance to static torsion (cl. 7.7.3)
- Resistance to soft and heavy body impact (cl. 7.7.4)
- Receiving and feeding back linkage signals (cl. 7.8)
- Fire resistance (cl. 7.10)
- Hose stream resistance (cl. 7.11)
- Fire resistance – Locks and hinges (Annex B)
|
| CMA | GB 12955-2008 Fire doors | - Moisture content of timber (cl. 6.3.2)
- Moisture content of wood-based panels (cl. 6.3.3)
- Steel thickness (cl. 6.3.4.2)
- Plate thickness of fire-rated hinges (cl. 6.4.2)
- Installation of cover strips (cl. 6.4.6; No separate report for this item)
- Appearance (cl. 6.5; No separate report for this item)
- Door leaf mass (cl. 6.6)
- Dimensional tolerances (cl. 6.7)
- Form and position tolerances (cl. 6.8; Door leaves up to 1500 mm × 2500 mm (twist and bow along the width or height))
- Fit tolerances (cl. 6.9)
- Ease of opening and closing (cl. 6.10.1; No separate report for this item)
- Door leaf opening force (cl. 6.10.2)
- Reliability (cl. 6.11)
- Fire resistance (cl. 6.12)
- Fire resistance – Fire-rated locks (Annex A)
- Fire resistance – Fire-rated hinges (Annex A)
- Fire resistance – Fire door coordinators (Annex C)
- Fire resistance – Fire-rated flush bolts (Annex D)
|
From our CNAS accreditation scope and our CMA approval (China's mandatory approval for inspection and testing bodies, needed for reports used in mainland China), as of 2026-10. Items not listed are outside the scope; ask our engineers whether they can be tested.
Frequently asked questions
Can you test to both the 2008 and 2024 editions?
Yes. The main items of the 2024 edition are within our CNAS accreditation and CMA approval scope; the items of the 2008 edition are within our CMA approval scope. The clauses are listed in the scope table below.
Can hardware such as locks and hinges be fire tested on its own?
Yes. Fire resistance of locks and hinges to GB 12955-2024 Annex B is within our CNAS scope; fire resistance of fire-rated locks, hinges, door coordinators and bolts to Annexes A, C and D of the 2008 edition is within our CMA approval scope.