Japan FDMA Notice No. 303, Annex 1

Fire and Disaster Management Agency (Japan), Operation of the storage and handling of lithium-ion storage batteries (Notice No. 303, fully revised by Notice No. 200 of 2 July 2024), Annex 1: Criteria for fire-resistant storage boxes; Hazardous Materials Safety Techniques Association (KHK), Test confirmation criteria for fire performance and structural requirements of fire-resistant storage boxes for lithium-ion batteries

Japan sets two fire tests for fire-resistant storage boxes and enclosures holding lithium-ion batteries: the first checks that fire does not get through the wall, the second that heat does not reach the box next to it. We can carry out both tests; they are not currently within our accreditation.

Available, outside accreditation scope We can carry out the first and second tests. They are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.

Why the requirement exists

In Japan the electrolyte of lithium-ion batteries is regulated as a hazardous material, and storing more than the designated quantity makes a site a hazardous materials facility. On 2 July 2024 the Fire and Disaster Management Agency fully revised its Notice No. 303 of 2011 through Notice No. 200: where batteries are kept in fire-resistant storage boxes (or under fire-resistant enclosures) that meet Annex 1, and the hazardous material in each box is below the designated quantity among other conditions, the multiples of the designated quantity need not be added up box by box. Annex 1 sets the tests these boxes must pass.

The notice is advice issued under Article 37 of the Fire Defence Organisation Act and is applied by local fire departments.

The two fire tests

Fire-resistant storage boxes must be made of materials that pass the first and second tests. Both use the standard heating curve T = 345 log₁₀(8t + 1) + 20, with specimens at least 30 cm on a side.

TestMethodPass criteria (60 minutes from the start)
First testOne specimen on the furnace, heated on one side; the unexposed side is observedNo flame ejection lasting more than 10 s, no flaming lasting more than 10 s, and no crack or other damage that flame can pass through, on the unexposed side
Second testTwo specimens facing each other no more than 4 cm apart, like two neighbouring boxes; one is heated and the unexposed side of the other is measuredTemperature at the measuring point not above 80 ℃ at 60 minutes

Enclosures with openings, such as vents and connector ports, must pass both tests at the openings too.

Besides fire performance, Annex 1 sets structural conditions: no gaps through which flame or heat passes easily, no tipping when fully loaded and tilted 15°, strength when stacked (a safety factor of 3 or more as a guide), strength for mechanical handling (for example the JIS Z 0200 drop test, method B), and marking on the box.

Our article Japan's testing regime for fire-resistant lithium-ion battery storage boxes explains the background.

Testing at Huahui

We can carry out the first and second tests at our Shanghai main laboratory. They are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.

Available, not accredited

StandardTest items
FDMA Notice No. 303, Annex 1
Japan: criteria for fire-resistant storage boxes for lithium-ion batteries (FDMA Notice No. 303, Annex 1)
  • First test: single specimen fire resistance (60 min; no flame ejection, flaming or through-cracks on the unexposed face)
  • Second test: two specimens no more than 4 cm apart (unexposed-face temperature not above 80 ℃ at 60 min)

We can carry out these tests, but they are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark. If the results are for certification, check first that your certifier accepts them.

Frequently asked questions

Can you test the structural conditions, such as tilt, stacking and drop?

What we list are the first and second fire tests. For the 15° tilt, stacking strength, JIS Z 0200 drop and transport vibration conditions, ask our engineers first.

Can we get Japanese test confirmation directly?

Test confirmation in Japan is carried out by the Hazardous Materials Safety Techniques Association (KHK), and under its criteria the performance tests are normally witnessed. If you need KHK test confirmation, check the arrangements with us before placing the order.