EN 1364-1: non-loadbearing walls
For walls and partitions that carry no load, with or without glazing: steel-stud partitions, sandwich panel walls, modular building walls, and the wall panels and joints of battery energy storage enclosures and data centre modules.
The specimen is mounted on a vertical furnace and exposed on one side to the EN 1363-1 standard fire curve, with furnace pressure controlled as EN 1363-1 requires. The test records:
- Integrity (E): cotton pad, gap gauges and sustained flaming.
- Insulation (I): mean temperature rise on the unexposed face no more than 140 K, maximum no more than 180 K.
- Radiation (W): needed for an EW classification. We do not measure it.
EN 1364-2: ceilings
For ceilings that have their own fire resistance, independent of the floor above. The specimen is installed on a horizontal furnace and exposed from below or from the void above, again against integrity and insulation criteria.
How it fits with other European standards
- General furnace conditions and criteria: EN 1363-1.
- Doors, shutters and openable windows: EN 1634-1.
- Loadbearing floors and roofs: EN 1365-2.
- Classification: EN 13501-2, for example EI 30, EI 60, EI 120.
Testing at Huahui
Tests run at our Shanghai main laboratory: walls on the vertical furnace, ceilings on the horizontal furnace. Specimen size, mounting and instrumentation are agreed before the test, based on the standard and your product.
Enclosures such as battery containers and data centre modules often need European, US and Chinese results together. We plan the specimens and test order across EN 1364, UL 263 / ASTM E119 and GB/T 9978; see enclosure fire resistance.
Our accredited scope
| Accreditation | Standard | Test items |
|---|---|---|
| CNAS | EN 1364-2:2018 Fire resistance tests for non-loadbearing elements — Part 2: Ceilings |
|
| CNAS | EN 1364-1:2015 Fire resistance tests for non-loadbearing elements — Part 1: Walls |
|
| CNAS | BS EN 1364-2:2018 Fire resistance tests for non-loadbearing elements — Part 2: Ceilings |
|
| CNAS | BS EN 1364-1:2015 Fire resistance tests for non-loadbearing elements — Part 1: Walls |
|
From our CNAS accreditation scope and our CMA approval (China's mandatory approval for inspection and testing bodies, needed for reports used in mainland China), as of 2026-10. Items not listed are outside the scope; ask our engineers whether they can be tested.
Frequently asked questions
Can you provide data for an EW classification?
No. EW needs radiation measured on the unexposed side, and radiation measurement is outside our accreditation scope. We provide the integrity and insulation data for E and EI classifications.
EN 1364-1 or EN 1634-1?
EN 1364-1 covers non-loadbearing walls and partitions, including walls with fixed glazing. Doors, shutters and openable windows are tested to EN 1634-1. Both are within our CNAS scope, so a wall system with a door can be planned as one programme.
Can you issue an EN 13501-2 classification report?
We issue the test report. Where an EN 13501-2 classification report from a notified body is needed, for example for CE marking, we can coordinate with a certification partner.