Energy storage and batteries

ASTM D93

ASTM D93, Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester

ASTM D93 determines the flash point of a liquid in a Pensky-Martens closed cup. UL 9540A requires flow batteries to have their electrolyte flash point measured with ASTM D93 or D3828 first, to decide whether the electrolyte is flammable. We have a closed-cup tester for this; it is not currently within our accreditation.

Available, outside accreditation scope We can determine closed-cup flash point to ASTM D93, mainly for flow battery electrolytes. It is not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.

Why flow batteries need a flash point

Flow batteries keep their electrolyte in tanks outside the stack, and fail differently from lithium-ion cells. The first step UL 9540A sets for them is to decide whether the electrolyte itself is flammable (2025 edition, clause 7.3.2.1):

  • For electrolytes with a high expected flash point and a viscosity of no more than 9.5 cSt at 25 °C, the flash point is determined with ASTM D3828 or ASTM D93; ASTM E502 guides the choice of method.
  • The heating rate may be as low as 4 °C per minute, and the test continues to 200 °C or until flammability is determined within the method's range.
  • The electrolyte tested is charged, representing full charge (100 % SOC), and is tested as soon as possible after charging to limit discharge.
  • In systems with two electrolytes, both are tested.
  • The flash point of each electrolyte is recorded; if none is observed, that is recorded and the test can end.

If a flash point is found, the thermal runaway propensity test of clause 7.3.2.2.2 follows.

Testing at Huahui

We have a Pensky-Martens closed-cup tester and can determine closed-cup flash point to ASTM D93, mainly for flow battery electrolytes. It is not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark.

For the other levels of UL 9540A testing, see UL 9540A.

Available, not accredited

StandardTest items
ASTM D93
Flash point by Pensky-Martens closed cup tester
  • Closed-cup flash point (mainly for flow battery electrolytes)

We can carry out these tests, but they are not currently within our CNAS / CMA accreditation, and reports carry no accreditation mark. If the results are for certification, check first that your certifier accepts them.

Frequently asked questions

What can you test for flow batteries under UL 9540A?

Our UL 9540A accreditation does not cover flow batteries. The electrolyte flammability step (clause 7.3.2.1, flash point) we can carry out, outside accreditation. If a flash point is found, the standard requires a thermal runaway propensity test (clause 7.3.2.2.2); ask our engineers about that first.